S.L. 545.41 Art. 16Temporary installations. S.L. 545.24.

In KraftAmtlicher Text

(1) A temporary installation shall have means of disconnection and protection as stipulated in the Electrical

Installations Regulations.

(2) Disconnection, protection and other necessary control equipment for temporary installations shall be housed within an insulated weatherproof enclosure (IP 54 or better) which shall also house the electricity meter and supply fuses installed by the distribution system operator. The applicant shall make arrangements to have the insulated weatherproof enclosure installed close to the distribution system operator supply point and beyond reach. The customer and, or the applicant shall be responsible for the insulated weatherproof enclosure, protection and control equipment together with the wiring from the insulated weatherproof enclosure to the point of consumption and shall ensure that the wiring does not present any obstruction or danger to third parties.

(3) The distribution system operator shall be responsible to connect the input cable to the source of supply and to disconnect it again after the event for which the application was made. Incoming and outgoing cables shall enter and leave respectively the insulated weatherproof enclosure from below and shall be glanded.

(4) Temporary service connections to temporary installations shall be provided for the duration and for the applicable fee as stipulated in item 4 of the Sixth Schedule.